| MRC | Criteria | Characteristic |
|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 15.470 INCHES MINIMUM AND 15.530 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 8.220 INCHES MINIMUM AND 8.280 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 11.590 INCHES MINIMUM AND 11.650 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 2.720 INCHES MINIMUM AND 2.780 INCHES MAXIMUM |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.340 INCHES MINIMUM AND 0.400 INCHES MAXIMUM |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 14.220 INCHES MINIMUM AND 14.280 INCHES MAXIMUM |
| AEGJ | SWITCH CONTACT ARRANGEMENT | DOUBLE POLE,DOUBLE THROW |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.720 INCHES MINIMUM AND 2.780 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.350 INCHES MINIMUM AND 0.410 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 10.970 INCHES MINIMUM AND 11.030 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 700.0 AMPERES AC AND 700.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 125.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC AND 65000.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 2100.0 TO 7000.0 AC AND 2100.0 TO 7000.0 DC ALL LOCATIONS |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND WEATHERPROOF |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CRTK | SWITCH TERMINAL TYPE | WIRE LEAD |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 6.0 AC AND 0.5 DC |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 600.0 AC AND 125.0 DC |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| PMLC | PRECIOUS MATERIAL AND LOCATION | CONTACTS SILVER |
| PRMT | PRECIOUS MATERIAL | SILVER |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |