Whether you are in the market for NSN parts, military and defense parts, aerospace parts, or other similar product solutions, Buy Military Fasteners is your one-stop shop with an expansive selection tracing back to premier manufacturers and entities that we trust. Thank you for taking an interest in part number A90278-35, a Munters Corporation item that is listed alongside the description “Circuit Breaker” and the NSN 5925013272730. As part number A90278-35 is ready for purchase on our website at any time, you are invited to fill out and submit the RFQ form provided on this page for the means of requesting a quote for your comparisons. All that we ask is that you supply us with crucial details such as your target price and expected shipping time frame, that way we can best customize a solution that caters to your unique requirements and constraints alike.
Note: We Will Not Share Your Information with Any Third Parties.
As customers explore our vast selection, they can take advantage of services like our CAGE Code search features or database filters to quickly locate products of interest for purchase. For example, part number A90278-35 is listed alongside the NSN 5925-01-327-2730, meaning that it also belongs to FSC 5925 Circuit Breakers. With this in mind, kick off procurement with us today with assurance that we can even fulfill your most difficult needs.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-01-327-2730 Item PartTypeName: CIRCUIT BREAKER | 5925 | 013272730 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| JD3150 | 5 | 2 | 5 |
| MRC | Criteria | Characteristic |
|---|---|---|
| ADAQ | BODY LENGTH | 10.000 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 4.062 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 8.375 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC AND 10000.0 DC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.125 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC AND 150.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 750.0 TO 1500.0 AC AND 750.0 TO 1500.0 DC ALL LOCATIONS |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 480.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| PKDW | PACKAGED UNIT WEIGHT | 10.000 POUNDS |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.